Multiquip DCA45SSKU3 Portable Generator User Manual


 
PAGE 16 — DCA45SSK/KU3 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (12/15/11)
GENERATOR
This MQ Power generator (Figure 3) is a high quality
portable (requires a trailer for transport) power source for
telecom sites, lighting facilities, power tools, submersible
pumps and other industrial and construction machinery.
ENGINE CONTROL PANEL
The “Engine Operating Panel” is provided with the following:
Engine Warning Lamp Module
• Oil Pressure Alarm Lamp
• Water Temperature Lamp
• Charging Alarm Lamp
• Pre-Heat Lamp
Fuel Gauge
Hour Meter
Speed Control Switch
Ignition Switch
GENERATOR CONTROL PANEL
The “Generator Control Panel” is provided with the following:
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter Change-Over Switch
Voltage Regulator
3-Pole, 125 amp Main Circuit Breaker
“Control Box” (located behind the Gen. Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Selector Switch
OUTPUT TERMINAL PANEL
The “Output Terminal Panel” is provided with the following:
Two 250 VAC output receptacles (CS-6369), 50 amps
Two auxiliary circuit breakers, 250V @50 amps
Two 125 VAC output receptacles, (GFCI), 20 amps
Two GFCI circuit breakers, 125V@ 20 amps
Five output terminal lugs (3Ø power)
OPTIONS
Battery Charger
Water Heater
Low Coolant Level Switch/Indicator
Camlock Connectors
OPEN DELTA EXCITATION SYSTEM
This generator is equipped with the state of the art “Open-
Delta” excitation system. The open delta system consist
of an electrically independent winding wound among
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectified and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the configuration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fixed ceiling” and responds
according the demands of the required load.
ENGINE
This generator unit incorporates an Kubota V3800-DI-T-E3B
diesel engine. This engine is designed to meet every
performance requirement for the generator. Reference
Table 2 for engine specifications.
In keeping with MQ Power’s policy of constantly improving
its products, the specifications quoted herein are subject
to change without prior notice.
ELECTRIC GOVERNOR SYSTEM (OPTION)
The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.
EXTENSION CABLES
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 6) as a
guide for selecting proper extension cable size.
GENERAL INFORMATION