Multiquip DCA25USIXF Portable Generator User Manual


 
1
DCA25USIXF/DCA25USI2XF — OPERATION AND PARTS MANUAL — REV. #2 (07/26/11) — PAGE 23
Figure 13. Connecting Loads
Connecting Loads
Loads can be connected to the generator by the UVWO terminal
lugs or the convienience receptacles. (See Figure 13). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the UVWO output terminals from overload, a 3-pole,
60 amp,
main
circuit breaker is provided. Make sure to switch
ALL
circuit breakers to the "OFF" position prior to starting the
engine.
Over Current Relay
An
over current relay
(Figure 14) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 14. Over Current Relay
OUTPUT TERMINAL PANEL
This fuse has current running through it
any time the engine is running. This fuse
is NOT connected to the main circuit
breaker of the generator. Attempting to
replace the fuse with the engine and/or
generator operating could result in
electrocution
and
severe bodily harm
. ALWAYS turn the unit completely
off before attempting to replace or handle this fuse.
DANGER