Multiquip DCA-25SSIU2 Portable Generator User Manual


 
DCA-25SSIU2 (60 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (01/27/06) — PAGE 35
1
DCA-25SSIU2 (60 HZ)— GENERATOR START-UP PROCEDURE
Figure 47. Ammeter (No Load)
12. The ammeter (Figure 47) will indicate zero amps with no
load applied. When a load is applied, this meter will
indicate the amount of current that the load is drawing
from the generator.
9. The generator's frequency meter (Figure 44) displays
the 60 cycle output frequency in HERTZ.
10. The generator's voltage meter (Figure 45) displays the
120 VAC in VOLTS. If the voltage is not within the specified
frequency tolerance,
Figure 45. AC Voltmeter
Figure 44. Frequency Meter (Hz)
11. Use the voltage adjustment control knob (Figure 46) to
increase or decrease the desired voltage.
Figure 46. Voltage Adjusted Control Knob
13. The engine oil pressure gauge (Figure 48) will indicate
the oil pressure (kg/cm
2
)
of the engine. Under normal
operating conditions the oil pressure is between 28 ~71
psi (193 ~490 kPa).
Figure 48. Oil Pressure Gauge
14. The coolant temperature gauge (Figure 49) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature is between 165 and
203 degrees Fahrenheit (74 ~ 95 degrees Celsius).
Figure 49. Coolant Temperature Gauge
Figure 50. Engine Tachometer
15. The tachometer (Figure 50) will indicate the speed of
the engine when the generator is operating. Under normal
operating conditions this speed is approximately 1800
RPM’s.