Multiquip DCA220SSCU Portable Generator User Manual


 
PAGE 24 — DCA220SSCU/4i 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (10/25/12)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage change-over board
(Figure 12). To obtain some of the voltages as listed in
Table 7 (see below) will require a fine adjustment using
the voltage regulator (VR) control knob located on the
control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 12) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Figure 12. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage
change-over board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Change-Over Board
3-Phase 240/139V Position
Voltage Change-Over Board
3-Phase 480/270V Position
Line-Line
208V 220V 240V 416V 440V 480V
Line-Neutral 120V 127V 139V 240V 254V 277V
Voltage Change-Over Board Single-Phase 240/120V Position
Line-Neutral/
Line-Line
120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Maximum Amps
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 8. Generator Maximum Amps
Model
DCA220SSCU/
DCA220SSCU4i
Rated Voltage Maximum Amps
Single Phase 120 Volt 488.9 amps (4 wire)
Single Phase 240 Volt 244.4 amps (4 wire)
Three Phase 240 Volt 529 amps
Three Phase 480 Volt 264 amps