GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 12). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fi ne adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 12) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Voltage Change-Over BoardFigure 12.
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Voltages AvailableTable 7.
Three Phase
(Switchable)
200V 220V 416V 440V
Single Phase
(Switchable)
115V 127V 240V 254V
Maximum Amps
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
Generator Maximum AmpsTable 8.
Rated Voltage Maximum Amps
Single Phase 100 Volt 98 amps (4 wire)
Single Phase 200 Volt 48 amps (4 wire)
Three Phase 200 Volt 104 amps
Three Phase 400 Volt 52 amps