QT036
kW RATING 36/35
ENGINE SIZE 2.4LiterInline4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz kW - LP Amps KW - NG Amps CB Size
120/208V,3-phase,0.8pf 36 125 35 121 150
120/240V,3-phase,0.8pf 36 108 35 105 125
277/480V,3-phase,0.8pf 36 54 35 52 60
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Singlephaseor2083-phase 63
480V3-phase 84
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) Natural Gas Propane
(ft
3
/hr.) (gal/hr.) cuft/hr
Exercisecycle 87 0.96 35.2
25%ofratedload 156 1.67 60.8
50%ofratedload 282 3.0 110
75%ofratedload 392 4.2 153
100%ofratedload 503 5.4 196
ENGINE COOLING
Airflow(inlet air including alternator and combustion air) ft
3
/min. 2,200
Systemcoolantcapacity USgal. 2.5
Heatrejectiontocoolant BTU/hr. 135,000
Max.operatingairtemp.onradiator °C(°F) 60(150)
Max.ambienttemperature °C(°F) 50(140)
COMBUSTION AIR REQUIREMENTS
Flowatratedpower60Hz cfm 106
SOUND EMISSIONS IN DBA
Exercisingat7meters 58
Normaloperationat7meters 64
EXHAUST
Exhaustflowatratedoutput60Hz cfm 300
Exhausttemp.atmuffleroutlet °F 1075
ENGINE PARAMETERS
RatedsynchronousRPM 60Hz 1800
HPatratedKW 60Hz 56
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
TemperatureDeration
3%forevery10°Cabove-°C 25
1.65%forevery10°Fabove-°F 77
AltitudeDeration
1%forevery100mabove-m 915
3%forevery1000ft.above-ft. 3000
OPERATING DATA
QT036
RATING: Allthreephaseunitsareratedat0.8powerfactor.Allsinglephaseunitsareratedat1.0powerfactor.STANDBYRATING:Standbyratings
applytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.Thereis
nooverloadcapabilityforthisrating.RatingsareinaccordancewithISO-3046-1.Designandspecificationsaresubjecttochangewithoutnotice.
KWratingisbasedonLPGFuelandmayderatewithnaturalgas.