Generac Power Systems COMMERCIAL SERIES Portable Generator User Manual


 
COMMERCIAL 60 kW
KW RATING 60
ENGINE SIZE 3.0 Liter V-6
GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size
120/240V, single phase, 1.0 pf 60 250 300
120/208V, 3-phase, 0.8 pf 60 208.4 250
120/240V, 3-phase, 0.8 pf 60 180.6 200
277/480V, 3-phase, 0.8 pf 60 90.3 100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase 120
480V 3-phase 141
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane) Natural Gas Propane
(ft
3
/hr.) (gal/hr.) cu ft/hr
Exercise cycle 123 1.34 48.7
25% of rated load 260 2.84 103.3
50% of rated load 500 5.46 198.6
75% of rated load 700 7.64 277.9
100% of rated load 960 10.48 381.3
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air) ft
3
/min. 3,280
System coolant capacity US gal. 2.5
Heat rejection to coolant BTU/hr. 270,000
Max. operating air temp. on radiator °C (°F) 60 (150)
Max. ambient temperature °C (°F) 50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 180
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode 63
db(A) @ 23 feet at normal operating load 71
EXHAUST
Exhaust flow at rated output 60 Hz cfm 494
Exhaust temp. at muffler outlet °F 1,050
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 3600
HP at rated KW 60 Hz 94
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C 25
1.65% for every 10 °F above - °F 77
Altitude Deration
1% for every 100 m above - m 183
3% for every 1000 ft. above - ft. 600
OPERATING DATA
COMMERCIAL 60 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance
with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient
temperature, altitude, engine power and condition, etc.
COMMERCIAL SERIES