Generac QT04524ANSX Portable Generator User Manual


 
MAINTENANCE ALERT CHART
CONDITION 1.6 CHERY 2.4/1800 MITSU 2.4/3600 MITSU 4.2 FORD
Change oil & filter alert 3mo/30hrs break-in
1yr/100hrs
3mo/30hrs break-in
1yr/100hrs
3mo/30hrs break-in
1yr/100hrs
3mo/30hrs break-in
1yr/100hrs
Inspect/clean air inlet &
exhaust alert
3mo/30hrs break-in
6mo/50hrs
3mo/30hrs break-in
6mo/50hrs
3mo/30hrs break-in
6mo/50hrs
3mo/30hrs break-in
6mo/50hrs
Change / Inspect air filter
alert
1yr/100hr 1yr/100hr 1yr/100hr 1yr/100hr
Inspect spark plugs alert 1yr /100hrs 1yr /100hrs 1yr /100hrs 1yr /100hrs 1yr /100hrs
Change / Inspect spark
plugs alert
2yr/ 250hr 2yr/ 250hr 2yr/ 250hr 2yr/ 250hr
Inspect Accessory drive
alert
3mo/30hrs break-in
1yr /100hrs
3mo/30hrs break-in
1yr /100hrs
3mo/30hrs break-in
1yr /100hrs
3mo/30hrs break-in
1yr /100hrs
Coolant change & flush 1yr /100hrs 1yr /100hrs 1yr /100hrs 1yr /100hrs
Inspect battery alert 1yr /100hrs 1yr /100hrs 1yr /100hrs 1yr /100hrs
OVERVOLTAGE ALARM
If the generator voltage rises above 110% for >3 seconds, an
alarm will be issued.
If the generator voltage rises above 130% for >0.2 seconds, an
alarm will be issued.
INTERNAL FAILURE SHUTDOWN ALARM
Any internal failure that can be detected such as corrupted
firmware will cause this shutdown alarm. This alarm cannot be
cleared.
CANBUS ALARM
Where applicable, if the Canbus communications link fails to com-
municate, a “Canbus alarm” will be generated. This only applies
to systems with external ignition modules. The alarm may be
generated if:
1. The physical link is broken.
2. The ignition module fails or resets.
3. The Nexus module fails or resets.
IGNITION ALARM
When an ignition alarm occurs, a generic message “Ignition Fault”
will be displayed as the fault code.
MAINTENANCE WARNING
When a maintenance period expires, a warning message will be
posted. The warning can be reset by hitting the Enter key. Resetting
will clear the warning and reset the maintenance counters for the
condition annunciated. The history log will reflect the maintenance
warning.
ALARM CANCEL
When the generator is shut down due to a latching alarm, the Auto
/Off/ Manual switch must be set to the off position and the ENTER
key pressed to unlatch any active fault and clear the corresponding
fault alarm message.
COMMON ALARM RELAY
The common alarm relay will be activated if there is a shutdown
alarm. It will not activate on warnings or indicate that the Auto/Off/
Manual switch is in the OFF position. The OFF position will clear
the alarms and the relay. The relay will not be used to indicate a
generator is not activated.
MAINTENANCE ALERTS
Maintenance alerts will be provided for these conditions (see the
Maintenance Alert Chart).
SERVICE SCHEDULE ‘A’
Inspect Accessory drive alert 1yr /100hrs
Coolant change & flush 1yr /100hrs
Inspect spark plugs alert 1yr /100hrs
Change oil & filter alert 1yr /100hrs
Inspect battery alert 1yr /100hrs
Change / Inspect air filter alert 1yr /100hrs
SERVICE SCHEDULE ‘B’
Change / Inspect spark plugs alert 2yr/ 250hr
8-6
CntrlNex001 Rev. A 05/10
Control Panel