8/10/14kW
8/10/14kW switch options
®
Model 005870-1 (8 kW) Model 005871-1 (10 kW) Model 005872-1 (14 kW)
No. of Poles 2 2 2
Current Rating (amps) 100 100 100
Voltage Rating (VAC) 250 250 250
Utility Voltage Monitor (fixed)
-Pick-up
-Dropout
80%
60%
80%
60%
80%
60%
Return to Utility approx. 15 sec. approx. 15 sec. approx. 15 sec.
Exerciser weekly for 12 minutes Standard Standard Standard
UL Listed Standard Standard Standard
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
10
3
3
1
1
-
-
12
5
3
-
1
1
-
14
4
6
1
-
1
-
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000 10,000 10,000
EZ Switch™ Features
• Electrically operated, mechanically-held contacts
for fast, positive connections.
• Rated for all classes of load, 100% equipment
rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to
resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on
the 100 amp switch.
• Pre-wired 30 foot (9.1 meter) whip to connect to
the pre-wired external connection box.
• Pre-wired 2 foot (0.61 meter) whip, color coded to
connect into the existing electrical panel.
Mechanical Dimensions (in inches)
Current
Rating
No. of
Poles
Height Width Depth
H1 H2 W1 W2
7100 UL Listed 2 26.5 in 29.25 in 8.14 in 12.5 in
673mm 743mm 207mm 317.5mm 178mm
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
731.9
[28.8]
637.6
[25.1]
LEFT SIDE VIEW
642
[25.3]
76.2 [3.0]
PEA GRAVEL
MINIMUM
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
1218
[47.9]
FRONT VIEW
1226
[48.3]
H2
H1
W1
W2
H2
H1
W1
W2
®
Dimensions
Dimensions
Nexus Smart Switch™ Features
available on 10 & 14kW models only
• Includes Digital Load Management technology standard (DLM).
• Intelligently manages two air conditioner loads with no additional hardware.
• Up to four more large (240V) loads can be managed when used in
conjunction with DLM modules.
• Electrically operated, mechanically-held contacts for fast, clean
connections.
• Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
• Dual coil design.
• Service Rated.
• NEMA 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
Model 006051-1 (10kW) / 006052-1 (14kW)
No. of Poles 2
Current Rating (amps) 200
Voltage Rating (VAC) 250
Utility Voltage Monitor (fixed) (Function
of Nexus Controller)
-Pick-up
-Dropout
80%
60%
Return to Utility (Function of Nexus
Controller)
approx. 13 sec.
Exerciser weekly for 12 minutes
(Function of Nexus Controller)
Standard
UL Listed Standard
Enclosure Type NEMA 3R
Withstand Rating (Amps) 10,000
Lug Range 400MCM - #4
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
Inches 27.24 30.0 11.4 13.5 7.09