Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain points on the generator
subject to change based on installation parameters.
Generator
Model 005818-0 (6kW)
Rated Maximum Continuous Power Capacity (LP) 6,000* Watts
Rated Voltage 120 VAC (240 VAC capable w/kit)
Rated Maximum Continuous Load Current – 120 VAC 50 Amps (25 @240 VAC)
Main Line Circuit Breaker 50 Amps (25 after conversion)
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60Hz
Power Factor 1
Battery Requirement (not included) Group 26R 12 Volts and 525 Cold-cranking Amperes Minimum
Unit Weight (Pounds/Kilos) 387/175.5
Dimensions (L x W x H) Inches/mm 48 x 25 x 29 [1218 x 638 x 732]
Sound output in dB(A) at 23 ft. with generator operating at normal load 52
Engine
Type of Engine GENERAC OHVI
Number of Cylinders 2
Displacement 530cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valve
Ignition System Solid-state w/Magneto
Governor System Electronic
Compression Ratio 9.5:1
Starter 12 Vdc
Oil Capacity Including Filter (quarts/liters) 1.7Q/1.6L
Oil Reservoir Capacity (quarts/liters) 4.2Q / 4.0L
Operating RPM 2,600
Fuel Consumption
Liquid Propane ft
3
/hr (gal/hr)
1/2 Load
Full Load
30.8/0.85
48.2/1.32
Required fuel pressure to generator fuel inlet at all load ranges - 11 to 14 inches of water column for LP gas
For Btu content, multipy ft
3
/hr by 2520
Controls
2-Line Plain Text LCD Display Simple user interface for ease of operation.
Mode Switch
-Auto Puts unit in standby mode, waiting for inverter start call.
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Start with starter control, unit stays on.
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Smart Battery Charger Standard
Automatic Voltage Regulator w/Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fused Standard
Low Battery Protection Standard
50 Event Run Log Standard
Internal Fault Protection Standard
EcoGen™ - 6 kW specifications
6kW
®