50 - Cycle Burdens at Rated Voltages
RELAY
TYPES
VOLTAGE
RATING
TAP**SETTING VOLT-AMPS POWER
FACTOR
WATTS
IAV51D 345 A(28) 31.9 0.36 11.4
B(42) 28.3 0.56 15.8
C(70) 21.0 0.79 16.6
D(112) 12.8 0.93 11.9
IAV51K 67 A(5.4) 28.8 0.29 8.4
IAV52K B(7.5) 26.6 0.45 12.1
C(12.5) 21.1 0.71 14.9
D(20) 16.0 0.86 13.7
115 No Taps 25.0 0.41 10.1
IAV52C 199 No Taps 25.4 0.28 7.0
345 No Taps 31.9 0.36 11.4
**Minimum pickup volts
TABLE IIIB
60 - Cycle Burden at Rated Voltages
RELAY
TYPES
VOLTAGE
RATINGS
TAP**SETTINGS VOLT-AMPS POWER
FACTOR
WATTS
1AV51D 115 A(10) 0.46 0.99 0.46
B(15) 0.62 1.0 0.62
C(25) 0.96 1.0 0.96
D(40) 1.48 1.0 1.48
IAV51D 199 A(16) 0.41 0.94 0.38
IAV52D B(24) 0.56 0.98 0.55
C(40) 0.89 0.99 0.88
D(64) 1.38 1.0 1.37
IAV51D 345 A(28) 0.48 0.86 0.41
B(42) 0.66 0.95 0.62
C(70) 1.02 0.98 1.01
D(112) 1.4 0.99 1.4
IAV51K 67 A(5.4) 0.43 0.91 0.39
IAV52K B(7.5) 0.57 0.96 0.55
C(12.5) 0.92 0.98 0.91
D(20) 1.47 0.99 1.46
115 No Taps 0.36 0.78 0.28
IAV52C 199 No Taps 0.41 0.94 0.38
345 No Taps 0.48 0.86 0.41
TABLE IIIB