Emerson SDN 10-24-480C Telescope User Manual


 
Technical Specications
Input
Nominal Voltage 380–480 V ac, 3Ph
Power Factor (PFC) EN61000-3-2 Class A
Inrush Current <25 A
Nominal Frequency 50/60 Hz
Output
Nominal Voltage 24 V (Adjustable from 24–28 V dc)
Current 10 A
Power 240 W
Power Boost 1.5 x nominal current for 4 s
Hold-up Time
>20 ms (full load, 380 V ac input @ Tamb +25°C) to
95% output voltage
Tolerance <2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature Drift <1%
Initial Voltage Setting 24.5 V ± 1%
Ripple <50 mVpp
Power Back Immunity 35 V dc
Parallel Operation Switch selectable
Overvoltage Protection >30.5 V dc, but <33 V dc auto recovery
Standards, Certications
Emissions
EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011,
EN55022 Radiated and Conducted including Annex A, EN61000-3-2
Immunity
EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level
4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4
Level 4 input and Level 3 output, EN61000-4-5 Isolation Class
4, EN61000-4-11, SEMI F47 Sag Immunity, EN61000-4-8,
EN61000-4-34, Transient protection according to VDE 0160/W2
over entire load range
Approvals
cULus Listed: UL 508, CSA C22.2 No. 107.1; : UL
60950-1/CSA C22.2 60950-1 2
nd
edition, UL 60079-15 and CAN/
CSA-E60079-15, Class I, Zone 2, AEx nC IIC Gc, Ex nC IIC U
hazardous locations; CE: IEC60950-1:2005 2
nd
edition, EN60950-
1:2006+A11:2009; ATEX: II 3 G Ex nC IIC Gc, DEMKO 11
ATEX 1105449U; EN60079-0:2009, EN60079-15:2010
Environmental Data
Ambient Temperature
Storage/Shipment: -40°C to +85°C
Operating: -25°C to +60°C at full load. Linear
derating to 50% of rated load from +60°C to +70°C
maximum. Convection cooling; no forced air required.
Degree of Protection IP20 (EN60529)
Recommended Minimum
Installation Clearance
25 mm above and below; 25 mm left and right. Do not
obstruct air ow.
Weight 1.54 lb. (700 g)
Technical Support
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
Datos Técnicos
Entrada
Voltaje Nominal 380–480 V ac, 3Ph
Factor de Potencia (PFC) EN61000-3-2 Clase A
Arranque <25 A
Frecuencia Nominal 50/60 Hz
Salida
Voltaje Nominal 24 V (Ajustable from 24–28 V dc)
Corriente 10 A
Potencia 240 W
Elevación de Potencia 1.5 x la corriente nominal por 4 s
Tiempo de Retención
>20 ms (la carga llena, 380 V ac entrada @ Tamb + 25°C)
a 95% de voltaje de salida
Tolerancia <± 2% en conjunto
• Regulación de Línea <0.5%
• Regulación de Carga <0.5%
• Desviación de Tiempo y Temp <1%
Ajuste Inicial de Voltaje 24.5 V ± 1%
Rizo <50 mVpp
Inmunidad de Potencia Inversa 35 V dc
Operación Paralela Interruptor seleccionable
Protección de Sobre Voltaje >30.5 V dc, pero <33 V dc recuperación automática
Estándares, Certicaciones
Emisiones
EN61000-6-2:2001, EN61000-6-3:2001, Clase B EN55011,
EN55022, Radiada Conducida incluida en el Anexo A, EN61000-3-2
Inmmunidad
EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Nivel 4,
EN61000-4-3 Nivel 3, EN61000-4-6 Nivel 3, EN61000-4-4 Nivel 4
entrada y nivel salida, EN61000-4-5 Aislamiento clase 4, EN61000-
4-11, SEMIF47 Inmunidad a Picos, EN61000-4-8, IEC61000-4-34,
Protección contra Transientes de acuerdo a VDE 0160/W2 sobre
todo el rango de la carga
Aprobaciones
cULus Listada: UL 508, CSA C22.2 No. 107.1; : UL
60950-1/CSA C22.2 60950-1 2
a
edición, UL 60079-15 and CAN/
CSA-E60079-15 Clase I, Zona 2, AEx nC IIC Gc, Ex nC IIC U
sitios peligrosos; CE: IEC60950-1:2005 2
a
edición, EN60950-
1:2006+A11:2009; ATEX: II 3 G Ex nC IIC Gc, DEMKO 11
ATEX 1105449U; EN60079-0:2009, EN60079-15:2010
Datos Ambientales
Temperatura Ambiente
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -25°C a +60°C en
carga llena. Lineal derating a 50% de la carga valorada
de +60°C a +70°C máximo. La convección que refresca;
ningún aire forzado requirió.
Grado de Protección IP20 (EN60529)
Espacio Libre Mínimo
recomendado de Instalación
25 mm por encima y por debajo; 25 mm izquierda y
derecha. No obstruya ujo aéreo.
Peso 1.54 lb. (700 g)
Servicio Técnico
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
Données Techniques
Entrés
Valeur Nominale 380–480 V ac, 3Ph
Facteur de Puissance (PFC) EN61000-3-2 Classe A
Inrupption <25 A
Fréquence Nominale 50/60 Hz
Sortie
Valeur Nominale 24 V (Adjustable from 24–28 V dc)
Courant 10 A
Puissance 240 W
Puissance de Survoltage 1.5 x valeur nominale pendant 4 s
Temps de Tient
>20 ms (le chargement plein, 380 V ac d’entrée @
Tamb + 25°C) à 95% tension de production
Tolérance <± 2% en général
• Régulation de Ligne <0.5%
• Régulation de Charge <0.5%
• Décalage Temps et Température <1%
Réglage Initial du Courant 24.5 V ± 1%
Ondulation <50 mVpp
Contre Aliment. en Retour 35 V dc
Opération Parallèle Interrupteur à sélectionner
Protection Contre la Surtension >30.5 V dc, mais <33 V dc récupération automatique
Normes, Autorisations
Emissions Dégagées
EN61000-6-2:2001, EN61000-6-3:2001, Classe B EN55011,
EN55022 Conduites Annexe A incluse, EN61000-3-2
Immunité
EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Niveau 4,
EN61000-4-3 Niveau 3, EN61000-4-6 Niveau 3, EN61000-4-4
Niveau 4 alimentation et niveau 3 sortie, EN61000-4-5 classe
isolation 4, EN61000-4-11, SEMIF47 immunité sag, EN61000-4-
8, IEC61000-4-34, Transitoire Protection selon VDE 0160/W2
sur gamme de charge entière
Approbations
cULus Enuméré : UL 508, CSA C22.2 No. 107.1; : UL
60950-1/CSA C22.2 60950-1 2
nd
édition, UL60079-15 and CAN/
CSA-E60079-15 Classe I, Zone 2, AEx nC IIC Gc, Ex nC IIC U
lieux dangereux; CE : IEC60950-1:2005 2
nd
édition, EN60950-
1:2006+A11:2009; ATEX : II 3 G Ex nC IIC Gc, DEMKO 11
ATEX 1105449U; EN60079-0:2009, EN60079-15:2010
Données Climatiques
Température Ambiante
Stockage/transport : -40°C to +85°C
Pleine charge nominale : -25°C à +60°C au
chargement plein. Linéaire derating à 50% de
chargement évalué de +60°C à +70°C maximum. La
convection qui refroidit ; aucun air forcé a exigé.
Degrés de Protection IP20 (EN60529)
Installation Dégagement
Minimum recommandé
25 mm au dessus et au dessous; 25 mm à gauche
et à droite. Ne pas encombrer du ux d’air.
Poids 1.54 lb. (700 g)
Assistance Technique
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
LED Diagnostics
LED OK
Loss of
AC
Low AC No DC
High
Load
Overload Hot Too Hot
Input Green --- Yellow --- Green Green Green Green
Output Green --- Green --- Yellow Yellow Green ---
Alarm --- --- --- --- Yellow Red Yellow Yellow
Diagnostic DEL
DEL OK
Perte
de AC
AC bas
Pas de
DC
Charge
Importante
Surcharge Chaud
Trés
Chaud
Entrée Vert --- Jaune Vert Vert Vert Vert Vert
Sortie Vert --- Vert --- Jaune Jaune Vert ---
Alarme --- --- --- Rouge Jaune Rouge Jaune Jaune
Diagnósticos LED
LED OK
La Perdida
de AC
AC baja
No
DC
Alta
Carga
Sobrecarga Caliente
Muy
Caliente
Entrada Verde --- Amarillo --- Verde Verde Verde Verde
Salida Verde --- Verde --- Amarillo Amarillo Verde ---
Alarma --- --- --- --- Amarillo Rojo Amarillo Amarillo