Chicago Electric 92456 Portable Generator User Manual


 
SKU 92456 For technical questions, please call 1-800-444-3353. Page 11
5. Place the Generator as close as possible to the electrical tools and equipment
being powered to reduce the length of extension cords.
6. If the Generator in located indoors the Engine exhaust must be ventilated to the
outdoors using leakproof, heat resistant, flexible, metal, flex tubing.
GENERATOR SUPPORT AND MOUNTING
1. Mount the Generator on a concrete slab capable of supporting the weight of the
Generator. The slab must extend on all sides beyond the Frame (41B) by at least
one foot. Contact a cement contractor for slab specifications if necessary. Attach
the Frame to the concrete slab using 3/8” diameter expansion anchor bolts (not
supplied).
GROUNDING THE GENERATOR
1. NOTE: It is recommended that only a trained and licensed electrician perform
this procedure.
2. Connect a #6 AWG grounding wire (not included) from the Ground Connector (8)
on the Generator to a grounding rod (not included) that has been driven at least
24 inches deep into the earth. The grounding rod must be an earth-driven copper
or brass rod (electrode) which can adequately ground the Generator.
(See Figure B, next page.)
OPERATING INSTRUCTIONS
NOTE: For additional references to the parts listed in the following pages, refer to the
Assembly Diagrams on pages 19 and 21.
Pre-Start Checks:
1. Check to make sure the Engine’s Power Switch (2) is in its “OFF” position.
(See Figure B, next page.)
2. IMPORTANT ! Prior to first using the Generator, the Engine MUST be filled
with approximately 3/4 (0.63) quart of a high quality SAE 10W-30 grade en-
gine oil. To do so, unscrew and remove the Engine’s Oil Dipstick (65A) located
at the bottom of the Engine Crankcase. Fill the Engine’s Crankcase until the oil
level is level with the upper marked line on the Dipstick. Then, screw the Dip-
stick back into the Oil Fill Hole. (See Figure C, next page.)