Briggs & Stratton PRO6500 01933 Portable Generator User Manual


 
9
BSPP Generator
RECEPTACLES
The generator will be equipped with one or more of the
following receptacles:
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volts AC at 30 Amps (or
greater) (Figure 5).You can use the same 4–wire cord if you
plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
30 Amps for 120 Volts; 7,200 watts of power (7.2 kW) at
30 Amps for 240 Volts.The outlet is protected against
overload by a push–to–reset circuit breaker and/or a 2 pole
GFCI circuit breaker.
120/240 Volt AC, 20 Amp Locking
Receptacle
Use a NEMA L14-20 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volts AC at 20 Amps (or
greater) (Figure 6).You can use the same 4-wire cord if you
plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 2,400 watts of power at
20 Amps for 120 Volts; 4,800 watts of power (4.8 kW) at
20 Amps for 240 Volts.The outlet is protected against
overload by a push–to–reset circuit breaker and/or a 2 pole
GFCI circuit breaker.
Figure 6 — 120/240 Volt AC, 20 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-20
Ground (Green)
Figure 5 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
DO NOT overload the generator. See “Don’t Overload
Generator”.
Receptacles may be marked with rating value greater
than generator output capacity.
CAUTION