4-12 Operation MN2417
Alarms
Following alarms are available:
Sensor fail (FLS) see Table 4-5
Sensor fail is detected when measured value is 6% out of selected sensor characteristic.
Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN) see Table 4-5
When warning comes up, only alarm outputs and common warning output are closed.
Shut down (SD) see Table 4-5
When the shut−down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and
common shutdown output are closed. Active or not reset protection disables start.
Table 4-5 Possible Warnings
Events specification Protection type
Wrn Oil press WRN
Sd Oil press SD
Wrn Water temp WRN
Sd Water temp SD
Wrn Wtemp Low WRN
Wrn Fuel Level WRN
Sd Fuel Level SD
Battery voltage <, > WRN
Battery flat SD
Start fail SD
Vgen <, > SD
Vgen unbl SD
Fgen <, > SD
Igen unbl SD
Overload SD
RPM over SD
RPM under SD
PickupFault SD
Stop fail SD
WrnServiceTime WRN
Emergency Stop SD
ECU Common Warning WRN
ECU Shutdown SD