Mitsubishi 6P-7PF Portable Generator User Manual


 
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS2500B
Type & Design
MGS original design, single bearing, 4 pole, screen protected, selfexciting, self regulating and brushless with fully
connected damper windings, salient pole rotors, A.C. exciter and rotating rectifier unit. Direct coupled to engine and
regreaseable bearing, direct drive centrifugal blower.
Enclosure: Drip-proof IP23
Winding System
Standard 6 wire winding provides 3 phase voltage. All windings are impregnated in vacuum pressure impregnated with a
special polyester resin.
Overspeed capability: 125% for 2 minutes
Insulation: Class 'H' of IEC
Temperature rise: Class 'H'
Voltage Regulator
Fully sealed, 3 phase RMS sensing AVR with built-in protection against sustained over-excitation. This de-excites the
generator after a minimum of 5 seconds.
Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0
allowing for a 4% engine speed variation
Voltage adjustment: +/- 6%
Wave form: Less than 5% deviation
Permanent Magnet Generator (PMG)
Electrically isolated from the main alternator stator windings powers AVR - sustaining approx. 250300% of short circuit
current at the AC generator output terminals for not more than 10 seconds by means of excitation voltage via AVR
Electrical Design
In accordance with BS5000 Part 3, VDE0530, UTE51100, NEMA MG1-22, CEMA, IEC34-1, CSA22.2, AS1359 and
JEC2100.
Telephone Influence Factor (TIF): Less than 50
Telephone Harmonic factor (THF): Less than 2%
Radio interference: Suppression is in line with the provision of BS800 and VDE Class G and N
Gen Set Option Features
ENGINE
Air Cleaner, paper element dry type
Battery Kit
Battery Charger
Anchor Bolts
FUEL
Fuel Day Service Tank
LUBRICATION
Lub. Oil Priming Pump
EXHAUST
Exhaust Silencer
Exhaust Flexible Pipe
GENERATOR
Space Heater
3 phase Sensing Auto Voltage Regulator
Power Factor Regulator
CONTROL PANEL
Diesel Generator Integrated Communication Synthesizer (DGICS-MII)
Auxiliary Control Panel
Remote Monitor Interface
SWITCHGEAR
Circuit Breaker MCCB & ACB
Reverse Power Relay
Power Systems Engine Section, Engine Sales Department
16-5, KONAN 2-CHOME, MINATO-KU, TOKYO 108-8215 JAPAN
TEL: 81-3-6716-4771 FAX: 81-3-6716-5854
Mitsubishi Heavy Industries, Ltd. serves for the customers with improved products continually.
Therefore specification and some materials will be changed without notice.
The International System of units (SI) is used in this publication.
MGS SERIES AC GENERATOR MODEL: MG-7PF